§ 59.202. Potable Water Level of Service.  


Latest version.
  • Potable Water level of service standards shall be used to determine whether levels of service for Potable Water are adequate to support the impacts of new development, pursuant to Part 3 of this Chapter.

    Potable Water Level of Service Standards. Potable Water level of service standards shall be as follows:

    Land Use Gallons Per Day without Reclaimed Water Gallons Per Day with Reclaimed Water Unit
    Single Family 325 160 Dwelling unit
    Multi Family 200 200 Dwelling unit
    Hotel 187 187 Room
    Commercial 0.13 0.13 Square feet
    Office 0.15 0.15 Square feet
    Industrial 0.22 0.22 Square feet
    Government 0.15 0.15 Square feet
    Hospital 0.22 0.22 Square feet
    These LOS standards shall be based on the average day demand.

     

    Minimum Pressure Demand Condition
    50 psi Average Day
    40 psi Peak Day
    25 psi Peak Day + Fire Flow

     

(Ord. of 9-16-1991, Doc. #25096; Ord. of 11-16-1992, Doc. #26149; Ord. No. 2017-4, § 1(Exh. A), 2-27-2017, Doc. #1702271206)